Steps 32 To 38 - Reset; Steps 39 To 43 - Operation - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

Programming
09
Emergency hold -EN 12094-1 4.20.3 b) compliant
Contact (1.2 kΩ) opened during pre-discharged warning time = extinguishing process is hold as long as the contact is
maintained opened. When contact is released, pre-discharged warning time restarts
Contact (1.2 kΩ) opened after actuator activation = no effect
Contact (1.2 kΩ) opened at any other time = "Automatic blocked". Return back to "Normal" condition is possible only with
the "Mode" push buton or with external button connected to a control input configured with step 49. 51 option 13
Application: for RU only

12.10 Steps 32 to 38 - Reset

Option
Step
Description
32
Reset: zones 1 and 2 operation
01
Alarm < 15 seconds after reset = "Alarm"
02
Alarm < 15 seconds after reset = "Fault"
(If an alarm occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel was before Reset).
33
Reset: zone 3 operation
01
Alarm < 15 seconds after reset = "Alarm"
02
Alarm < 15 seconds after reset = "Fault"
(If an alarm occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel was before Reset).
34
Reset: manual control input operation
01
Input enabled < 15 seconds after reset = "Alarm"
02
Input enabled < 15 seconds after reset = "Fault"
(If a manual release occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel was before
Reset).
35
Reset: monitored input 1 operation (discharged contact)
01
Input enabled < 15 seconds after reset = "Released"
02
Input enabled < 15 seconds after reset = "Fault"
(If a discharge contact activation occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel
was before Reset).
36
Reset: front panel key operation
01
Reset possible only after:
è
"Silence buzzer" and
è
"Silence sounders" and
è
"Flooding time"
02
Reset possible only after:
è
"Silence buzzer" and
è
"Silence sounders" and
è
"Flooding time" and
è
"Manual release" is reset and
è
"Discharged" contact is reset
37
Reset: control input 1 operation
01
Reset possible at any time (not EN 12094-1 and EN 54-2 compliant)
02
Reset possible only after:
è
"Silence buzzer" and
è
"Silence sounders" and
è
"Flooding time" and
è
"Manual release" is reset and
è
"Discharged" contact is reset
03
Reset possible only after flooding time
38
Reset during emergency hold
01
Reset is possible during "Emergency hold" (not EN 12094-1 compliant)
02
Reset is not possible during "Emergency hold"

12.11 Steps 39 to 43 - Operation

Option
Step
Description
39
Buzzer in state "Emergency hold/abort" operation
70
Building Technologies
Fire Safety
A6V10257473_e_en_--
2015-03-04