Monitored output 5 : activation duration
Applicable, with the same options as at step 02, only if this output is set to "Process as actuator" (see step 14).
04
Flooding time
The flooding time sets the duration the gas concentration must be maintained. During this time, the reset function is not possible.
Adjustable from 0 to 30 minutes by step of 1 minute
Default: 1 minute
00
30 seconds
01
1 minute
02
2 minutes
03
3 minutes
¦
¦
28
28 minutes
29
29 minutes
30
30 minutes
Building Technologies
Fire Safety
Programming