17
Special functions
17.1
Anticipated Silence Sounders
17.2
Anticipated Reset
17.3
Extract fan
Building Technologies
Fire Safety
The functions described in this chapter must be used only during commissioning
and/or maintenance. It is not allowed to use these functions during normal
operation. The following access code shall not be delivered to the customer.
This function is used to stop/start the Sounders during the pre-discharged warning
time.
Procedure
1. Enable operating access level 2,
2. Press and hold down "Silence buzzer" key (6), then enter the code 2 1 1 2 4 3
on the numeric keypad:
è
the sounders stop
3. Press the "Silence/Re-sound Sounders" key (5)
è
the sounders start again
This function is used to reset the system without having to wait the end of the
programmed flooding time.
Procedure
1. Enable operating access level 2
2. Press and hold down the « Silence buzzer » key (6), then enter
the code 2 4 4 2 1 3 on the numeric keypad:
è
"Pre-discharged warning time" ends immediately and the reset can be carried
out
This function allows starting / stopping the extract fan. The extract fan provides a
means to vent a room of extinguishing gases but prevents the gases from being
vented during a discharge. The extract fan can be de-activated only with the
"Reset" key.
1. Enable operating access level 2
2. Enter the code 1 2 3 1 on the numeric keypad:
è
Extract fan starts
3. Press the "Reset" key (7)
è
Extract fan stops
–
Extract fan cannont be started during the pre-discharged warning time and during the flooding time
Extract fan is automatically switched off as soon as an extinguishing process is started
–