Steps 10 To 14 - Monitored Outputs 1 To 5 - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

02
Remote transmission blocked
Application: avoid the remote transmission when the system is controlled by the operator
12.6

Steps 10 to 14 - Monitored outputs 1 to 5

Option
Step
Description
10
Monitored output 1 : select the operation
01
Processing as "Sounders" (see step 05 and paragraph 12.1)
Active until "Silence/Re-sound" or "Reset" via non-monitored control input 1
99
Do not use this option
11
Monitored output 2 : select the operation
01
Processing as "RT-alarm" (see step 06 and paragraph 12.1)
02
Processing as "Fire controls A" (see paragraph 12.1)
03
Processing as "Fire controls B" (see paragraph 12.1)
04
Processing as "Fire controls C" (see paragraph 12.1)
05
Processing as "Sounders" (see steps 05 and 10 and paragraph 12.1)
06
Processing as "Sounders" (see steps 05 and 10 and paragraph 12.1), except that:
- is activated continuously in state "Activated"
- is deactivated in state "Emergency Hold/Abort"
Application: additional wire for second tone sounder
07
Active in state "Mechanical blocked"
Application: use of a specific Warning Panel showing that extinguishing is blocked
08
Active in state "Automatic blocked" or "Manual blocked"
Application: specific Warning Panel for "Manual Blocked" or "Automatic Blocked"
09
Active in state "Automatic blocked" and "Manual blocked"
Application: specific Warning Panel for "Manual Blocked" and "Automatic Blocked"
99
Not used (no EOL required)
12
Monitored output 3 : operation
Fire alarm
01
Not activated
02
Not activated
03
Not activated
04
Pulsating
05
Not activated
99
Not used (no EOL required)
13
Monitored output 4 : operation
01
Processing as "Actuators", activated at the end of the pre-discharged warning time
02
Processing as "Actuators", activated at the beginning of the pre-discharged warning time
Application: activation of a pneumatic delay device
14
Monitored output 5 : operation
01
Processing as "Actuators", activated at the end of the pre-discharged warning time (see step 02 and paragraph 12.1)
02
Processing as "Actuators", activated at the beginning of the pre-discharged warning time (see step 02 and paragraph 12.1)
03
Processing as "Fire controls A" (see paragraph 12.1)
04
Processing as "Fire controsl B" (see paragraph 12.1)
05
Processing as "Fire controls C" (see paragraph 12.1)
06
Processing as "Fire control", activated 5s before the end of the pre-discharged warning time (see paragraph 12.1)
07
Processing as "Fire control", activated 10s before the end of the pre-discharged warning time (see paragraph 12.1)
08
Processing as "Fire control", activated 15s before the end of the pre-discharged warning time (see paragraph 12.1)
09
Processing as "Extract fan" (see paragraph 12.1)
10
Processing as "Fire damper" (see steps 63 and 64 and paragraph 12.1)
11
Processing as "Door holder" (see paragraph 12.1)
12
Active in state "Mechanical Blocked"
Application: use of a specific Warning Panel showing that extinguishing is blocked
Building Technologies
Fire Safety
Evacuation
Continuous
Pulsating
Pulsating
Continuous
Pulsating
Released
Continuous until "Reset"
Continuous until "Reset"
Continuous until "key 4" is pressed after "Reset"
Continuous until "Reset"
Pulsating until "Reset"
Programming
65
A6V10257473_e_en_--
2015-03-04