Programming
07
7
08
8
09
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
61
Configure Repeater silence buzzer
01
Silence buzzer on XC10 do not silence buzzer on repeater terminal
02
Silence buzzer on XC10 silences buzzer on repeater terminal
12.19 Step 62 - Loss of agent in multi-sector application
Option
Step
Description
62
XCA1031 loss of agent contact programming
01
Contact (1.2 kΩ) normally closed when cylinders pressure/weight is correct
02
Contact (1.2 kΩ) normally opened when cylinders pressure/weight is correct
12.20 Steps 63 to 64 - Fire damper
Option
Step
Description
This output is used to connect a fire damper that must be that must be opened a few seconds before the gas release and closed once the
gas is released. For safety reasons, it is not recommanded to connect an over-pressure flap to this output (In case the line is broken,
damage may occur on the room structure).
63
Select start of activation
Example: if the configured "Pre-discharged warning time" is 30s, options 02..03 are automatically reduced to 30s
01
Activated at the beginning of the "Pre-discharged warning time"
02
Activated 50s before the end of the "Pre-discharged warning time"
03
Activated 40s before the end of the "Pre-discharged warning time"
04
Activated 30s before the end of the "Pre-discharged warning time"
05
Activated 20s before the end of the "Pre-discharged warning time"
06
Activated 10s before the end of the "Pre-discharged warning time"
07
Activated at the end of the "Pre-discharged warning time"
Select the activation duration after the end of the "Pre-discharged warning time"
64
01
0 second
02
2 seconds
03
4 seconds
04
6 seconds
05
8 seconds
06
10 seconds
07
15 seconds
08
20 seconds
09
25 seconds
10
30 seconds
11
35 seconds
12
40 seconds
13
45 seconds
74
Building Technologies
Fire Safety
A6V10257473_e_en_--
2015-03-04