Siemens XCI2001-U1 Mounting & Installation
Siemens XCI2001-U1 Mounting & Installation

Siemens XCI2001-U1 Mounting & Installation

Releasing module

Advertisement

Quick Links

XCI2001-U1
Releasing module
Mounting
Installation
A6V10315050_e_en_--
2016-10-27
Building Technologies
Siemens Industry, Inc.

Advertisement

Table of Contents
loading

Summary of Contents for Siemens XCI2001-U1

  • Page 1 XCI2001-U1 Releasing module Mounting Installation Building Technologies A6V10315050_e_en_-- 2016-10-27 Siemens Industry, Inc.
  • Page 2 Issued by: Siemens Industry, Inc. Building Technologies Division 8 Fernwood Road Florham Park, NJ 07932 Tel. +1 973-593-2600 www.sbt.siemens.com/FIS Edition: 2016-10-27 Document ID: A6V10315050_e_en_-- © Siemens Industry, Inc., 2015 2 | 14 Building Technologies A6V10315050_e_en_-- Siemens Industry, Inc. 2016-10-27...
  • Page 3: Table Of Contents

    Views ....................... 7 Pin assignments for releasing module ............8 X5 plug connection for releasing relay output ............ 8 Indicators ....................10 Adjusting elements for releasing module .............11 Technical data..................12 FCC Statement ..................13 3 | 14 Building Technologies A6V10315050_e_en_-- Siemens Industry, Inc. 2016-10-27...
  • Page 4 4 | 14 Building Technologies A6V10315050_e_en_-- Siemens Industry, Inc. 2016-10-27...
  • Page 5: Description

    Automatic or manual activation ● Dual-channel control ● Supervision of releasing circuit (wiring as class A or class B circuit) ● Supports several valve systems ● Suited to indoor applications (not wet rooms) 5 | 14 A6V10315050_e_en_-- Building Technologies Siemens Industry, Inc. 2016-10-27...
  • Page 6: Mounting

    2. Fasten the releasing module to the threaded standoffs (2) in the back box using the two fixing screws (4). 3. Wire up the releasing module according to the pin assignment. 6 | 14 Building Technologies A6V10315050_e_en_-- Siemens Industry, Inc. 2016-10-27...
  • Page 7: Views

    Flashing: Releasing module is active * For Class A wiring, both S1 and S2 must be in the same position at all times when used to disarm or arm the circuit. 7 | 14 A6V10315050_e_en_-- Building Technologies Siemens Industry, Inc. 2016-10-27...
  • Page 8: Pin Assignments For Releasing Module

    REL_CIR2 (+) Relay output for releasing 2 REL_CIR2 (-) Relay output for releasing 2 Admissible cable cross-section: 12…18 AWG, unshielded XCI2001-U1 supports two Class B circuits or one Class A circuit as shown below: Class B wiring REL-EOL SOLENOID REL_CIR1...
  • Page 9 Note 2 Loop wires must be terminated directly onto the SOLENOID *REL-EOL: Terminating resistor 24 kΩ and diode (Siemens part number 500-696359) The maximum length of line of the relay connections is limited to a resistance of 3.5 Ω. 9 | 14...
  • Page 10: Indicators

    Releasing circuit 2 activated Green Status of processor Off (steady) Processor is not running Flashing Processor is running On (steady) Processor is not running * Not applicable for Class A wiring. 10 | 14 Building Technologies A6V10315050_e_en_-- Siemens Industry, Inc. 2016-10-27...
  • Page 11: Adjusting Elements For Releasing Module

    3 - 2 Activated No degrade operation allowed (Default) 1 - 2 Deactivated Degrade operation allowed Jumper X3 must agree with the panel configuration or a trouble will be displayed. 11 | 14 A6V10315050_e_en_-- Building Technologies Siemens Industry, Inc. 2016-10-27...
  • Page 12: Technical Data

    2.5 Ω Minimum voltage at the coil DC 20.4 V Mechanical data Dimensions (W x H) ~3.25 x 4.75" / ~8.25 x 12.05 cm Weight Approx. 3.2 oz / 90 g 12 | 14 Building Technologies A6V10315050_e_en_-- Siemens Industry, Inc. 2016-10-27...
  • Page 13: Fcc Statement

    Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference. 13 | 14 A6V10315050_e_en_-- Building Technologies Siemens Industry, Inc. 2016-10-27...
  • Page 14 Issued by © Siemens Industry, Inc., 2015 Siemens Industry, Inc. Technical specifications and availability subject to change without notice. Building Technologies Division 8 Fernwood Road Florham Park, NJ 07932 +1 973-593-2600 www.sbt.siemens.com/FIS Document ID: A6V10315050_e_en_-- FS20/FS920 SAP order no.: A5Q00050764...