Detectors Connected To Xc10 Panel - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

18.2

Detectors connected to XC10 panel

18.2.1 Connections variant 1
Building Technologies
Fire Safety
Sinteso / Cerberus PRO operating terminal when the "XC10 zone" element
4:Input 'Blocked' is activated
-
Resetable from Sinteso / Cerberus PRO
If this option is selected, the "XC10 zone" element 1:Output 'Reset' is activated
for 3 seconds each time a "Reset" command is operated from the Sinteso /
Cerberus PRO panel.
-
Enable / Reset time:
If this option is selected, the Sinteso / Cerberus PRO panel checks inputs
"Discharged" and "Pre-alarm" during the "Reset time". If these inputs are back
to the normal condition, the Sinteso / Cerberus PRO panel is reset. For a proper
operation, "Reset time" must be always set to 10s.
Usually, "XC10 zone" input elements are assigned to FDCIO222 module inputs.
Depending on FDCIO inputs status, the following messages are displayed on
Sinteso / Cerberus PRO panel:
FDCIO
"XC10 zone"
Input
input
assigned
"Discharged"
IN1
"Fault"
IN2
"Pre-alarm"
IN3
"Blocked"
IN4
Following XC10 zone messages can be displayed:
- "Exting. discharged"
- "Fault"
- "Exting.pre-alarm"
- "Aut+man ext.OFF XC"
- "Aut.ext.OFF XC"
- "Aut+man ext.OFF FC" (XC10 blocked from the Sinteso / Cerberus PRO panel)
- "Aut.ext.OFF FC" (XC10 blocked from the Sinteso / Cerberus PRO panel)
Following controls are possible from the Sinteso / Cerberus PRO panel:
- Reset
- Block autom.+manual
- Block autom.
Connection to Sinteso / Cerberus PRO panels
Message displayed on Sinteso / Cerberus PRO panel
Short circuit
1k15
"XC10 zone
"XC10 zone
Exting.
Exting.
discharged"
discharged"
"XC10 zone
(normal)
Fault"
"XC10 zone
"XC10 zone
Exting.pre-
Exting.pre-
alarm"
alarm"
"XC10 zone
"XC10 zone
Aut+man
Aut+man
ext.OFF XC"
ext.OFF XC"
3k01
1k15 + 3k01
(normal)
(normal)
"XC10 zone
"XC10 zone
Fault"
Fault"
(normal)
(normal)
(normal)
(normal)
A6V10257473_e_en_--
Line open
"IN1 Fault"
"XC10 zone
Fault"
"IN3 Fault"
"XC10 zone
Aut.ext.OFF
XC"
91