Commissioning; Powering; Monitored Control Outputs 4 And 5 Calibration - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

13

Commissioning

13.1

Powering

13.2 Monitored control outputs 4 and 5 calibration

Building Technologies
Fire Safety
Before commissioning, ensure that:
-
the control unit is correctly mounted on a fixed support
-
all detector bases are correctly connected
-
all monitored lines are correctly connected and equipped with respective EOL
-
all accessory or optional parts are present
-
FCP1004-E power supply setting correspond to the mains voltage
-
mains voltage is available
-
batteries are installed, but not connected yet
-
installation of extinguishing devices (piping, cylinders, manometers, discharged
contact ...) is completed
1. switch on the mains circuit breaker
2. connect the batteries and, if necessary, the total loss of power cable (see 7.2)
3. select presetting appropriate to your country need (see paragraph 12.2)
4. set, if necessary, user functions (see paragraphs 12.3 to 12.18)
5. calibrate monitored control outputs 4 and 5 (see paragraph 13.2)
6. eliminate possible faults (see paragraph 14.2)
7. select operating access level 2
8. enter the code 2 1 4 3 2 3 on the keyboard then press "Enable/Disable
actuators" (10) key within 5 seconds:
display shows "CAL", "Operating access" led goes out (= calibration process
start)
9. wait until the buzzer sounds twice (=end of calibration process). Two possibilities
can arise:
è
calibration success:
"Fault" (2) and "Actuators" (20) led goes out
display shows "OK" for a few seconds, then goes out, "Disable" led (6) goes
out, "Operating access" led lights up again
è
calibration failure:
display shows "4E5E" or "4E.. " or " ..5E" for a few seconds then "ECAL"
"Fault" led (2), "Disable" led (6) and "Actuators" led (20) led remain lit up,
"Operating access" lights up again
check the cable connections of the output concerned (4 and/or 5)
re-start the procedure at point 2
è
At first commissioning, monitored control outputs 4 and 5 not being calibrated, will display a fault
indication:
"Actuators" led (20) and "Fault" led (2) flash fast
"Disable" led (6) lit up fix
Display shows "ECAL" (= Error calibration)
è
Calibration cannot be started if the XC10 is in alarm or activated condition
Calibration fails if the resistance value measured during the calibration process is equal to 0 Ω
è
or > 900 Ω
è
Calibration of monitored output 5 is not carried out if this output is programmed "Not used"
Commissioning
77
A6V10257473_e_en_--
2015-03-04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc1005-aXc1003-a

Table of Contents