15.8
Zone test
15.9
Manual release test
Building Technologies
Fire Safety
Zone test is used to check each connected detector.
Procedure
1. Enable operating access level 2
2. Press 2 times the key "Disable/Test/Enable" (12 to 14) corresponding to the
zone to be tested:
è
The yellow led of the zone (26, 28, 30) and the yellow led "Test" (7) flash
slowly
è
The yellow led "Disable" (6) lights up fixed
3. Switch a detector to alarm condition and check that the red led (25, 27, 29)
corresponding to the tested zone and the red led on the detector flash during
10s end go out automatically
4. Repeat operation 3 for each detector connected on the line
5. Press the key "Disable/Test/Enable" (12 to 14) to end the test
- During the test, no acoustic or output are activated
- When the extinguishing triggering zones are in test condition, the yellow led "Automatic blocked"
(16) is activated
Manual release test is used to check each DM1103-L release button.
Procedure
1. Enable operating access level 2
2. Press 2 times the key "Disable/Test/Enable" (15):
è
The yellow led of the manual release (32) and the yellow led "Test" (7) flash
slowly
è
The yellow led "Disable" (6) lights up fixed
3. Trigger a release button and check that the red led (31) corresponding to the
tested zone and the red led on the release button flash during 10s end go out
automatically
4. Reset the release button
5. Repeat operation 3 and 4 for each release button connected on the line
6. Press the key "Disable/Test/Enable" (15) to end the test
- During the test, no acoustic or output are activated
- When the manual release is tested, the yellow led "Manual blocked" (14) is activated
Reset all release buttons before leaving the test condition, otherwise the
CAUTION
extinguishing process may be triggered (depending on programming).