Repeaters - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

9.4

Repeaters

9.4.1
Description
Building Technologies
Fire Safety
The repeater connects to the XC10 extinguishing control panel and provides
remote status indication and remote control.
-
Up to 16 repeaters can be connected to each XC10 control panel
-
The number of repeaters connected to an XC10 is configured with programming
step 60
-
Data transmission path called RTNet is using RS485 physical layer
-
Maximum line lengh: 1200 m
-
Repeaters can be powered either from the XC10 24V output or from an external
power supply
-
Repeaters are supervised and the XC10 indicates a fault condition if one
repeater is disconnected with identification address
-
In case repeaters are accidentally disconnected, an audible signal is indicated
thanks to a small battery inside each repeater
-
2 variants are available:
-
repeater display: XT/XTA1001-A1 provides remote status indication
-
repeater terminal: XT/XTA1002-A1 provides remote status indication and
remote control
-
Each variant can be delivered either in a plastic housing (XT100x-A1) or with a
19" mounting plate (XTA100x-A1)
Fig. 35
XT/XTA1001-A1 – XT/XTA1002-A1 description
Accessories
51
A6V10257473_e_en_--
2015-03-04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc1005-aXc1003-a

Table of Contents