Programming
68
100 seconds
69
105 seconds
70
110 seconds
71
115 seconds
72
120 seconds
99
Same as pre-discharged warning time of automatic release
66
Configure Manual Release "pre-discharge" warning time to overwrite Automatic release "pre-discharge" warning time
01
Manual release "pre-discharge" warning time does not overwrite Automatic release "pre-discharge" warning time
02
Shorter Manual release "pre-discharge" warning time overwrite longer Automatic release "pre-discharge" warning time
03
Following an automatic triggering signal, manual release overwrite emergency hold/abort (NFPA2001 compliant, EN12094-1
not compliant)
12.22 Step 67 – Operation if "Discharge" is activated in standby
67
Operation in case "Discharge contact" activated during standby condition
01
Actuators outputs are activated (concern XC10 lines 4 and 5, XCA1031 lines 1 and 2)
Note: cannot be used with Step8_Option4!!
02
Actuators outputs are not activated (concern XC10 lines 4 and 5, XCA1031 lines 1 and 2)
Application: for AT only