Steps 52 To 55 - Detection Zones - Siemens XC1001-A Installation And Maintenance Manual

Extinguishing control unit xc10 series
Hide thumbs Also See for XC1001-A:
Table of Contents

Advertisement

Programming
03
"Manual blocked"
04
"Automatic and manual blocked"
05
External device disabled
06
"RT-Alarm" and "RT-Fault" disabled
07
External device fault
08
External power supply fault
09
Fault on "RT-Fault" line from external device remote transmission (transmitter, for example)
10
Level 2 operating access
11
"Silence/Resound" sounders
12
No effect
13
Toggle function between "Automatic blocked" condition and "Normal" condition
Application: for RU only
Not compliant to EN12094-1 chapter 4.23.2 because input is not monitored
50
Non monitored control input 3
Same options as non monitored control input 2 – default = 12
51
Non monitored control input 4
Same options as non monitored control input 2 – default = 12
1)
State is maintained as long as a potential +24V is applied
2)
Pulse control (0.2 s minimum)
3)
Control must be possible through a level 2 access device only

12.14 Steps 52 to 55 - Detection zones

Option
Step
Description
52
Alarm verification: select zones (*)
01
No alarm verification
02
Zone 1
03
Zone 2
04
Zones 1 and 2
05
Zone 3
06
Zone 1, 2 and 3
(*)The alarm condition is enabled only after 2 consecutive alarms in less than 60 seconds (the 1st one is reset automatically). The
delay for the second alarm is 8 s. If the second alarm doesn't come within 60 s, the first alarm is automatically reset. The first
alarm is indicated by the red led during 2 s.
53
Automatic release: select zones combination
01
Alarm zone 1 AND Alarm zone 2
02
( Alarm zone 1 AND Alarm zone 2 ) OR ( Fault zone 1 AND Alarm zone 2 ) OR ( Alarm zone 1 AND Fault zone 2 )
03
Alarm zone 1 AND Alarm zone 2 AND Alarm zone 3
04
( Alarm zone 1 AND Alarm zone 2) OR Alarm zone 3
05
( Alarm zone 1 AND Alarm zone 3 ) OR ( Alarm zone 2 AND Alarm zone 3 ) OR ( Alarm zone 1 AND Alarm zone 2 )
06
Alarm zone 1 OR Alarm zone 2
07
Alarm zone 1
Care shall be taken using option 04, 06 and 07 as it triggers the extinguishing process on a single alarm
54
Zones disabling
01
Zone1 .. Zone 4 Disable/Test" is allowed
02
Zone1 .. Zone 4 Disable/Test" is not allowed
03
Zone 4 Disable/Test" is not allowed
04
Zone1 .. Zone 3 Disable/Test" is not allowed
05
Zone1 .. Zone 2 Disable/Test" is not allowed
55
Zone 3 : Fire alarm condition
01
"Fire alarm" condition indicated, RT-Alarm activated
02
"Fire alarm" condition indicated, RT-Alarm not activated
72
Building Technologies
Fire Safety
1) 3)
1) 3)
1)
1)
1)
("Reset" operation is required to eliminate the fault indication)
1)
1) 3)
2) 3)
1)
2) 3)
A6V10257473_e_en_--