3.5 Motor connections
MicroFlex e100 will operate with a large number of brushless servo motors. For information on
selecting Baldor servo motors please see the sales brochure BR1202, available from your local
Baldor representative. The motor must be capable of being powered by an inverter PWM output
- see section 8.1.3 for details. The motor can be connected directly to the MicroFlex e100 or
through a motor contactor (M-Contactor). The motor outputs are conditionally short-circuit proof.
Motors should ideally have a minimum inductance of 1 mH per winding; for motors with lower
inductance an output reactor may be fitted in series with the motor.
When using a Baldor motor, the parameters for managing motor overloads are configured
automatically by the Commissioning Wizard (see section 6.4.3). If they need to be changed, or
you are using an alternative motor, use the Parameters tool in Mint WorkBench (see section
6.5.2).
AC supply voltage
Output voltage range
Motor
Earth
U
V
W
* The threaded holes in the top and bottom of the case are for M4 bolts no longer than 11 mm (0.43 in) in length.
Do not connect supply power to the MicroFlex e100 UVW outputs. The
MicroFlex e100 might be damaged.
CAUTION
The motor leads U, V and W must be connected to their corresponding U, V or W
terminal on the motor. Misconnection will result in uncontrolled motor movement.
CAUTION
The motor power cable must be shielded for CE compliance. The connector or gland used at the
motor must provide 360 degree shielding. The maximum recommended cable length is 30.5 m
(100 ft).
Note: For CE compliance the motor earth/ground should be connected to the drive
earth/ground.
3-18 Basic Installation
Location
Connector X1
115 VAC, 1Φ
0-115 VAC, 3Φ
Connect motor
earth/ground to
protective earth
on top of drive.
See Note.
Optional motor
circuit contactors.
Figure 7 - Motor connections
230 VAC, 1Φ
0-230 VAC, 3Φ
Connect motor
earth/ground to
protective earth on
top of drive. *
Unshielded
lengths should
be as short as
possible.
www.baldormotion.com
230 VAC, 3Φ
0-230 VAC, 3Φ
MN1942