DeviceNet-Design
Input-Assemblies
Address
S1...S4
4, 1, 3
(factory setting)
S1...S4 + POS
4, 2, 3
(with POS:
current position)
„Address" in the table describes the data attribute of the assemblies
for read access (class, instance, attributes).
Output-Assembly
Address
Solenoid valve
4, 21, 3
SV 1 ... 3
Type 8681
Format of the Data attribute
value 0: OFF / value 1: ON
Byte 0:
Bit 0: position S1
Bit 1: position S2
Bit 2: position S3
Bit 3: position S4
Byte 0:
Bit 0: position S1
Bit 1: position S2
Bit 2: position S3
Bit 3: position S4
Bit 4...7: not used
Byte 1:
POS in mm
Format of the Data attribute
value 0: OFF / value 1: ON
Byte 0:
Bit 0: SV1
Bit 1: SV2
Bit 2: SV3
Bit 3...7: not used
10.9. Configuration of the Safety
Position of Solenoid Valves if Bus
Error
If the bus fails, the solenoid valve is switched to a programmable
safety position (factory setting: the solenoid valve is in the power-off-
state) - for details see manual, chapter „Configuration of the device".
The bus status LED „Network" on the electronic module specifies the
kind of error by color and blinking pattern - for details see manual,
chapter „Display of the Status LEDs in the event of a bus error").