Table 4-8
Supply voltage
Electrical isolation
Output voltage
Output current on signal "1"
S
at ambient temperature of
40_C
− Rated value
− Permissible value range
− Lamp load
S
at ambient temperature of
60_C
− Rated value
− Permissible value range
Switching rate
Load power supply (L+, M)
Here a 24-V load power supply must be connected. The unit will not operate if the
poles are reversed.
Note
Note the SIMATIC setup guidelines. In particular, the M terminal (reference poten-
tial) must be connected with the chassis ground of the programmable controller
(M terminal on the terminal block of the S7-300 CPU).
see manual S7-300 Programmable Controller, Hardware and Installation.
Danger
!
The 24 V load power supply should be a functional extra-low voltage with safe
isolation to EN60204-1, Section 6.4, PELV (with M grounding).
Note
Make sure that the interconnecting cable between power supply and load power
supply connection L+ and appropriate reference potential M does not exceed a
max. permissible length of 10 m.
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
Electrical parameters of digital outputs
24 V DC (allowable range: 20.4 − 28.8 V)
No
S
S
0.5 A (total current 2 A)
5 mA...0.6 A (over power supply range)
max. 5 W
0.1 A (total current 0.4 A)
5 mA...0.12 A (over power supply)
S
S
0 signal: Residual current max. 2 mA
1 signal: (Power supply −3 V)
Resistive load: max. 100 Hz
Inductive load: 0.25 Hz
Wiring
4-17