Starting up
7.1

Installation and wiring

Installation information
You can find information about how to install your module:
S In Chapter 3 of this manual
S In the manual S7-300 Programmable Controller, Hardware and Installation
Wiring information
You can find information about how to wire your module:
S In Chapter 4 of this manual
S In the manual S7-300 Programmable Controller, Hardware and Installation
Checklist
The checklist below will help you check important steps in the installation and para-
meterization of the FM 353 positioning module.
Table 7-1
Installation and wiring checklist
Step
Check
1
Slots
2
Shielding
3
Limit switches
4
Parameterize
7-2
Plug the module into one of the suitable slots.
Check the shielding of the FM 353 positioning module:
S
To ensure proper shielding, the module must be screwed down
firmly on the rail.
S
The shielding for shielded lines for digital I/O modules must be
connected to the shielding terminal element.
S
The shielding for the setpoint cable should not be grounded on
the drive-unit end.
Check the start/stop limit switches. The limit-switch connections must
be connected to the power section. The start/stop limit switches
should not be connected to the digital inputs.
Make sure the FM 353 positioning module setup is consistent with
the parameterization. Check in particular that the wiring of the digital
I/O modules matches the machine data.
What to do: