Number Of Input/Output Points And Maximum Number Of Input/Output Points; Calculation Of Number Of Input/Output Points - Mitsubishi FX3G SERIES User Manual

Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
6.3
Number of Input/Output Points and Maximum Number of Input/Output
Points
6.3.1

Calculation of number of input/output points

To obtain the total number of input/output points, count the input/output points of input/output powered
extension units/blocks and the input/output occupied points of special function blocks.
The number of remote I/O points on CC-Link network must be excluded.
1
Total the number of input/output points on the main unit and the number of
those on the input/output powered extension units/blocks.
To obtain the total number of input/output points, count the input points (X000 and more) and output
points (Y000 and more) of the main unit and input/output powered extension units/blocks.
The number of input/output points of each type of device is shown on the list below.
2
Count the input/output points of the remote I/O stations connected on FX
64CL-M network.
Add the number of remote I/O points to the number of input/output points from the main unit and
input/output powered extension units/blocks calculated in the above step.
3
Count the number of input/output occupied points of special function blocks.
The number of occupied input/output points per unit is 8.
The number of occupied input/output points of each type of device can be obtained by the following
formula or from the list shown below.
Number of special function
blocks
Number of special function
blocks
Observe the following instructions when using the following products.
• FX
-16CCL-M(CC-Link master)
2N
When more than one master station is connected, a remote I/O station cannot be connected to the 2nd and
following master stations.
FX
-64CCL
3U
Only one FX
3U
6.3 Number of Input/Output Points and Maximum Number of Input/Output
→ The list of numbers of input/output points is shown in Section 6.8.
→ For the remote I/O point calculation method, refer to the FX
→ For a list of occupied input/output points, refer to Section 6.8.
Number of points per unit
units
8 points
Each special function block
used for FROM/TO instructions
occupies eight input or output
points.
-64CCL unit can be connected to a single PLC main unit
6 Examination of System Configuration
Number of occupied
input/output points
points
=
Total number of
occupied input/
output points
1
2
3
4
-
2N
5
-64CL-M manual.
2N
6
7
8
9
10
57