Notes About Examples Of Wiring - Mitsubishi FX3G SERIES User Manual

Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
WIRING PRECAUTIONS
Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units.
Doing so may cause damage to the product.
Perform class D grounding (grounding resistance: 100
2
wire 2 mm
or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.3).
Do not wire vacant terminals externally.
Doing so may damage the product.
Connect the DC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.
When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
Make sure to properly wire the FX
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
-
The disposal size of the cable end should follow the dimensions described in this manual.
-
Tightening torque should be between 0.5 and 0.8 N•m.
Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
-
The disposal size of the cable end should follow the dimensions described in this manual.
-
Tightening torque should be between 0.22 and 0.25 N•m.
-
Twist the end of strand wire and make sure that there are no loose wires.
-
Do not solder-plate the electric wire ends.
-
Do not connect more than the specified number of wires or electric wires of unspecified size.
-
Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
-
The disposal size of the cable end should follow the dimensions described in this manual.
-
Tightening torque should be between 0.5 and 0.8 N•m.
13.1

Notes about Examples of Wiring

The examples of wiring are given under the following conditions.
• The input/output numbers are the actual numbers on the program. (They may differ from the numbers
shown on the product terminals.)
• Product input/output specifications
Check the product input/output specifications when using any example of wiring.
- Products only for sink input and products both for sink input and for source input are available.
• The examples of programming (applied instructions) are given based on the allocation of the input/output
numbers for wiring.
154
/FX
Series extension equipment in accordance with the following precautions.
2N
3U
→ For the example of positioning wiring, refer to the Positioning Control Edition.
→ For the applied instructions, refer to the Programming Manual.
13 Examples of Wiring for Various Uses
or less) to the grounding terminal on the main unit and extension units with a
13.1 Notes about Examples of Wiring

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents