10.5

Pulse Catch (M8170 to M8175)

The PLC (main unit) is provided with a pulse catch function and has 6 pulse catch input points.

10.5.1 Allocation of special memories to input numbers (ON duration of input signals)

Input number
X000
X001
X002
X003
X004
X005

10.5.2 Cautions for pulse catch

1. Non-overlap of input numbers
The input terminals X000 to X005 can be used for high-speed counter, input interruption, pulse catch, speed
detection (SPD) instructions and general-purpose input.
Take care not to overlap the input numbers.
Example:
When the C235, C241, C244, C246, C247, C249, C252 and C254 is used, X000 is occupied. Therefore, it is
impossible to use pulse catch input contact M8170.
128
→ For details on programming, refer to the programming manual.
Contact on sequence program
M8170
M8171
M8172
M8173
M8174
M8175
10 Input Wiring Procedures
10.5 Pulse Catch (M8170 to M8175)
ON duration of input signal
10 s or more
50 s or more
10 s or more
50 s or more