FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
PLC
Error
operation
code
at error
occurrence
Operation error [M8067(D8067)]
0000
No error
No jump destination (pointer) for CJ or CALL instruction
Label is undefined or out of P0 to P4095 due to indexing.
6701
Label P63 is executed in CALL instruction; cannot be used
in CALL instruction as P63 is for jumping to END
instruction.
6702
CALL instruction nesting level is 6 or more
6703
Interrupt nesting level is 3 or more
6704
FOR-NEXT instruction nesting level is 6 or more.
6705
Operand of applied instruction is inapplicable device.
Device number range or data value for operand of applied
6706
instruction exceeds limit.
File register is accessed without parameter setting of file
6707
register.
6708
FROM/TO instruction error
Continues
operation
6709
Other (e.g. improper branching)
6710
Mismatch among parameters
6730
Incorrect sampling time (T
Incompatible input filter constant ( )
6732
( < 0 or 100
6733
Incompatible proportional gain (K
6734
Incompatible integral time (T
Incompatible derivative gain (K
6735
(K
< 0 or 201
D
6736
Incompatible derivative time (T
6740
Sampling time (T
14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.6 Judgment by Error Codes and Representation of Error Codes
Contents of error
) (T
0)
S
S
)
) (K
< 0)
P
P
) (T
< 0)
I
I
D
)
K
)
D
) (T
< 0)
D
D
)
Scan time
S
Action
This error occurs in the execution of operation. Review the
program, or check the contents of the operands used in the
applied instructions.
Even if the syntax or circuit design is correct, an operation
error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100, the
timer T600 would attempt to be accessed. This would cause
an operation error since there is no T600 device available.
This error occurs in the execution of the operation.
Review the program, or check the contents of the
operands used in the applied instructions.
Check whether the specified buffer memories exist in the
equipment.
Check whether the extension cables are correctly
connected.
This error occurs in the execution of operation. Review the
program, or check the contents of the operands used in the
applied instructions.
Even if the syntax or circuit design is correct, an operation
error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100, the
timer T600 would attempt to be accessed. This would cause
an operation error since there is no T600 device available.
This error occurs when the same device is used within the
source and destination in a shift instruction, etc.
<PID instruction is stopped.>
This error occurs in the parameter setting value or operation
data executing PID instruction.
Check the contents of the parameters.
<Auto tuning is continued.>
The operation is continued in the condition "sampling time
(T
) = cyclic time (scan time)".
S
11
12
13
14
15
16
17
18
19
20