3. Output specifications (transistor output type)
Item
Output Points
Connection type
Output unit/type
External power supply
Output circuit insulation
Indication of output operation
Max. load
Open circuit leakage current
Min. load
Response time
Output circuit configuration
198
The total load current per common terminal
Resistance load
should be the following value.
4 output points/common terminal: 0.8A or
less
Inductive load
OFF ON
ON OFF
15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL
FX
-32ET-ESS/UL
2N
16 points
Removable terminal block (M3 screw)
Transistor/source output
5 to 30V DC
Photo-coupler insulation
Activation of the photo-coupler will light the LED indicator lamp on panel.
0.5A/point
12W/24V DC
0.1mA/30V DC
0.2ms or less/200mA (at 24V DC)
0.2ms or less/200mA (at 24V DC)
Load
Y
DC power
supply
+V
Fuse
A common number applies to the of [+V ].
15 Input/Output Powered Extension Units
FX
-48ET-ESS/UL
2N
24 points
0.5A/point
The total load current per common terminal
should be the following value.
4 output points/common terminal: 0.8A or
less
8 output points/common terminal: 1.6A or
less
-