Number Of Input/Output (Occupied) Points And Current Consumption; A] Main Units; B] Input/Output Powered Extension Units/Blocks - Mitsubishi FX3G SERIES User Manual

Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
6.8

Number of Input/Output (Occupied) Points and Current Consumption

The following tables show the number of input/output points or the number of input/output occupied points for
each type of device, along with the power supply type and current consumption values needed for selecting a
product.
• Number of input/output points or input/output occupied points on each type of device
• Output current of 24V DC service power supply of main units
• Output current of 5V DC power supply and 24V DC service power supply of input/output powered
extension units
• Current consumed by input/output extension blocks and special function blocks
The current consumption is determined differently in the following cases.
• In the input/output powered extension unit, 5V DC and internal 24V DC are supplied via extension cables.It
is necessary to calculate the current consumption.Subtract the current consumption of the internal 24V DC
from the 24V DC service power supply.
• The special function units/blocks connected to the AC power type main unit or to the 24V DC service
power supply terminal of the input/output powered extension unit consume the external 24V DC. Include
the current in the calculation of current consumption.
When the terminal is connected with an external power supply, the current is not included in the calculation
of current consumption.
6.8.1

[A] Main units

A
No.
AC power supply/24V DC input/transistor output type
FX
3G
FX
3G
A1
FX
3G
FX
3G
*1.
Each number inside ( ) indicates the number of occupied points.
Use numbers inside ( ) when calculating the total number of input/output points.
6.8.2

[B] Input/output powered extension units/blocks

1. Input/output powered extension units
B
No.
FX
2N
FX
2N
FX
2N
FX
2N
FX
2N
B1
FX
2N
FX
2N
FX
2N
FX
2N
72
Number of input/
Type
output points
[points]
-14MT/ES
14(16)
-24MT/ES
24(32)
-40MT/ES
40
-60MT/ES
60(64)
Number of input/
Type
output points
[points]
-32ER-ES/UL
32
-32ET-ESS/UL
32
-32ER
32
-32ES
32
-32ET
32
-48ER-ES/UL
48
-48ET-ESS/UL
48
-48ER
48
-48ET
48
6.8 Number of Input/Output (Occupied) Points and Current Consumption
Input/output
Input/output
[points]
*1
8/6(8)
*1
14(16)/10(16)
24/16
*1
36(40)/24
Input/output
Input/output
[points]
16/16
16/16
16/16
16/16
16/16
24/24
24/24
24/24
24/24
6 Examination of System Configuration
Output current (mA)
24V DC service power supply
400
Output current (mA)
24V DC service
5V DC power supply
power supply
690
250