INSTALLATION PRECAUTIONS
Use the product within the generic environment specifications described in Section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl
flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind.
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
Install the product securely using a DIN rail or mounting screws.
Terminal block
Main unit, FX
2N
special extension block/special adapter
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities.
Make sure to affix the expansion board with tapping screws.
Tightening torque: 0.3 to 0.6 N•m
Loose connections may cause malfunctions.
When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
Be sure to remove the dust proof sheet from the PLC's ventilation port when installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely to their designated
connectors.
Loose connections may cause malfunctions.
Connect the memory cassette, and expansion board board securely to their designated connectors.
Loose connections may cause malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause device failures or malfunctions.
-
Peripheral devices, expansion boards, and special adapters
-
Extension units/blocks and the FX Series terminal block
-
Battery and memory cassette
WIRING PRECAUTIONS
Connect the AC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.
Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or
wiring work.
Failure to do so may cause electric shock.
82
Series I/O extension unit/block, and FX
DIN rail only
/FX
Series
2N
3U
DIN rail or direct mounting
8 Installation In Enclosure
, H
S, SO
or NO
),
2
2
2
2