6.3.2

Maximum number of input/output points when CC-Link master is used

1. Calculation of maximum number of input/output points
When CC-Link master block is used, the following maximum number of input/output points can be connected.
Maximum number of
input/output points
384 points
Maximum number
of points
controllable on
system
(A): Number of input/output points of main unit
(B): Number of input/output points of input/output
powered extension units
(C): Number of input/output points of input/output
extension blocks
*1.
When seven 32-point type remote I/O stations are used, the number of CC-Link remote I/O points
reaches the maximum number.
The number of CC-Link points is calculated by the formula "32 points × number of stations" even when
remote I/O stations having less than 32 points are used.
For details, refer to FX
2. Procedures for calculating number of input/output points based on example of system
configuration
For the main unit, input/output powered extension units/blocks and CC-Link remote I/O stations, the number
of input/output points and the total number of points are restricted.
X000 to X027
X030 to X057
Main unit
extension unit
Y000 to Y027
Y030 to Y057
24/24
= 48 points
Number of input/output points occupied by special function units/blocks
0 points
Number of input/output points (128 points)
Number of input/output points (excluding remote I/O points on CC-Link) + Number of
82
Number of input/
output points
(A)(B)(C)(D)
Total number of
input/output points
For details, refer to Subsection 6.3.1.
-16CCL-M User's Manual.
2N
X060 to X077
Input/output
Input
powered
extension
block
24/24
16/0
= 48 points
= 16 points
Remote I/O
Remote I/O
(8 points)
(16 points)
input/output occupied points
Up to 256 points
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
Number of input/output occupied
points
(E)
units
+
Number of points occupied by
special function units/blocks
(D): Number of remote I/O points of FX
16LNK-M
(E): Number of input/output points occupied by special
function units/blocks
(F): Number of remote I/O stations (units) connected to CC-
Link master
X100 to X117
Input
Special
extension
function unit
block
16/0
8 points
= 16 points
CC-Link network
Remote I/O
(32 points)
128
144
160
Number of
remaining points
Number of
remaining
384 points or less in total
6 Examination of System Configuration
CC-Link remote I/O
× 8
(F) stations
points
+
Total number of points obtained by
formula "number of remote I/O
stations × 32 points" (The number is
multiplied by 32 points regardless of
the number of remote I/O points.)
FX
-16CCL-M
2N
8 points
Remote I/O
Remote I/O
(32 points)
(32 points)
224 256
32 points × 5 units = 160 points
points
Number of CC-Link input/output points
Up to 224 points
× 32
points
-64CL-M or FX
-
2N
2N
384 points