WIRING PRECAUTIONS
Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units.
Doing so may cause damage to the product.
Perform class D grounding (grounding resistance: 100
2
wire 2mm
or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.3).
Connect the DC power supply to the dedicated terminals specified in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.
Do not wire vacant terminals externally.
Doing so may damage the product.
When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
Make sure to properly wire the FX
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
-
The disposal size of the cable end should follow the dimensions described in this manual.
-
Tightening torque should be between 0.5 and 0.8 N•m.
or less) to the grounding terminal on the main unit and extension units with a
/FX
Series extension equipment in accordance with the following precautions.
2N
3U
15 Input/Output Powered Extension Units
11
12
13
14
15
16
17
18