Service cases - hardware

4.11 Double Motor Modules

4.11
Double Motor Modules
4.11.1

DMM status displays

Status displays
The Motor Module has the following status displays, which provide information about the
module state:
LED state
RDY
DC LINK
OFF
OFF
Green
OFF
Orange
Red
Orange
Orange
Red
Green/red
(0.5 Hz)
Green/red
-
(2 Hz)
Green/orange
or red/orange
DC link voltage
Hazardous DC link voltages may be present at any time regardless of the state of the
"DC Link" LED. The warning information on the components must be carefully observed!
158
Description, cause
The electronics power supply is missing or outside the
permissible tolerance range.
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is controlled irrespective of the corresponding
messages being reconfigured.
Firmware is being downloaded.
Firmware download has been completed. Wait for
POWER ON.
Component recognition via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
DANGER
Remedy
Check the line supply
voltage.
Remove the fault and
acknowledge
Carry out a POWER ON.
Hardware and Software
Service Manual, 03/2011, 6FC5397-5DP40-0BA0