Dnp / Iec 60870-5-104 Point Lists - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the T60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The T60 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
POINTS
a one-to-one basis.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the T60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
effect.
NOTE
k) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
 DNP / IEC104
 POINT LISTS
MESSAGE
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 BINARY INPUT / MSP
 POINTS
MESSAGE
MESSAGE
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the full range of
assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 ANALOG INPUT / MME
 POINTS
MESSAGE
MESSAGE
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
GE Multilin
setting specifies a time delay for the detection of dead network TCP connections. If
DNP TCP CONNECTION TIMEOUT


COMMUNICATIONS
DNP / IEC104 POINT LISTS
 BINARY INPUT / MSP
 POINTS
 ANALOG INPUT / MME
 POINTS


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off
T60 Transformer Protection System
5.2 PRODUCT SETUP
DNP NUMBER OF PAIRED CONTROL
setting for the changes to take
Range: see sub-menu below
Range: see sub-menu below
BINARY INPUT / MSP POINTS
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand

ANALOG INPUT / MME POINTS
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
5