5.10 TESTING

PATH: SETTINGS
 FORCE CONTACT
 OUTPUTS
5
The relay contact outputs can be pre-programmed to respond to the test mode.
If set to "Disabled", the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to "Energized", the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to "De-ener-
gized", the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to "Freeze", the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1
For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
"Latched" (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, contact input 1
should remain operational, contact inputs 2 and 3 should open, and contact input 4 should close. Also, contact output 1
should freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully opera-
tional. The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the
TESTING
TEST MODE
Make the following changes to configure the contact inputs and outputs. In the
and
INPUTS

FORCE CONTACT OUTPUTS

FORCE Cont Ip 1:
FORCE Cont Op 1:
and
FORCE Cont Op 4:
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as "Latched". Write the following FlexLogic equation:
Set the user-programmable pushbutton as latching by changing
PUSHBUTTONS
input 1 to initiate the Test mode, make the following changes in the
TEST MODE FUNCTION:
5-340

TESTING
FORCE CONTACT OUTPUTS
FORCE Cont Op 1
:Disabled
FORCE Cont Op 2
MESSAGE
:Disabled
FORCE Cont Op xx
MESSAGE
:Disabled
menu:
TEST MODE FUNCTION:
menus, set:
"Disabled",
FORCE Cont Ip 2:
"Freeze",
FORCE Cont Op 2:
"Disabled"
USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
"Enabled" and
TEST MODE INITIATE:
T60 Transformer Protection System
Range: Disabled, Energized, De-energized, Freeze
Range: Disabled, Energized, De-energized, Freeze
Range: Disabled, Energized, De-energized, Freeze
"Enabled" and
TEST MODE INITIATE:
"Open",
"Open", and
FORCE Cont Ip 3:
"De-energized",
FORCE Cont Op 3:
SETTINGS
to "Latched". To enable either pushbutton 1 or remote

SETTINGS
"
"
VO1
5 SETTINGS
5.10.3 FORCE CONTACT OUTPUTS
"
"
PUSHBUTTON 1 ON


SETTINGS
TESTING
FORCE CONTACT
"Closed"
FORCE Cont Ip 4:
"Energized",

PRODUCT SETUP
USER-PROGRAMMABLE
menu:
TESTING
TEST MODE

SETTINGS