5 SETTINGS
Select the
DIRECT I/O DATA RATE
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communica-
tions cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately
0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each 'bridge'.
Table 5–11: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
74
Channel 1
Channel 2
7L
Channel 1
Channel 2
7M
Channel 1
Channel 2
7P
Channel 1
Channel 2
7T
Channel 1
7W
Channel 1
Channel 2
7V
Channel 1
Channel 2
2A
Channel 1
2B
Channel 1
Channel 2
2G
Channel 1
2H
Channel 1
2I
Channel 1
Channel 2
2J
Channel 1
Channel 2
76
Channel 1
77
Channel 1
Channel 2
75
Channel 1
Channel 2
7E
Channel 1
Channel 2
7F
Channel 1
Channel 2
7G
Channel 1
Channel 2
7Q
Channel 1
Channel 2
7R
Channel 1
7S
Channel 1
Channel 2
The G.703 modules are fixed at 64 kbps. The
NOTE
GE Multilin
to match the data capabilities of the communications channel. All IEDs communicating
SUPPORTED DATA RATES
64 kbps
64 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps
64 kbps
64 kbps
128 kbps
128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
DIRECT I/O DATA RATE
T60 Transformer Protection System
5.2 PRODUCT SETUP
setting is not applicable to these modules.