GE T60 Instruction Manual page 182

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
Set
REMOTE DEVICE 1 ETYPE APPID
"0" in the example above.
Set the
configurable GOOSE 1 in this example, program this value as "GOOSEIn 1".
3.
Configure the Boolean data by making the following changes in the
settings menu:
INPUT 1
5
Set
REMOTE IN 1 DEVICE
Set
REMOTE IN 1 ITEM
item to remote input 1.
4.
Configure the analog data by making the following changes in the
settings menu:
INPUTS
Set the
IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE
Enter "Hz" for the
The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The T60 must be
rebooted (control power removed and re-applied) before these settings take effect.
The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in the
sending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting of
the sending device.
Remote input 1 can now be used in FlexLogic equations or other settings. The T60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between T60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains
the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the T60
(DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN sup-
port).
Set the
CONFIG GSE 1 FUNCTION
entered, return the
NOTE
PATH: SETTINGS
TRANSMISSION
 CONFIG GSE 1
 DATASET ITEMS
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: "GGIO1.ST.Ind1.stVal" and "GGIO1.ST.Ind1.q". The T60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
5-48
to match the ETHERTYPE application ID from the transmitting device. This is
value. This value represents the dataset number in use. Since we are using
REMOTE DEVICE 1 DATASET
to "GOOSEOut_1".
to "Dataset Item 2". This assigns the value of the GGIO3.ST.Ind1.stVal single point status
IEC61850 GOOSE ANALOG INPUT 1 UNITS
function to "Disabled" when configuration changes are required. Once changes are
CONFIG GSE 1 FUNCTION

PRODUCT SETUP
COMMUNICATIONS

CONFIGURABLE GOOSE
ITEM
GGIO1.ST.Ind1.stVal
ITEM
MESSAGE
GGIO1.ST.IndPos1.stV
ITEM
MESSAGE
None
ITEM 64:
MESSAGE
None
T60 Transformer Protection System
INPUTS/OUTPUTS
INPUTS/OUTPUTS
to "60.000".
setting.
to "Enabled" and restart the unit for changes to take effect.

IEC 61850 PROTOCOL

CONFIGURABLE GOOSE 1(8)
Range: all valid MMS data item references for
1:
Range: all valid MMS data item references for
2:
Range: all valid MMS data item references for
3:
Range: all valid MMS data item references for
5 SETTINGS

REMOTE INPUTS

IEC 61850 GOOSE ANALOG
GSSE/GOOSE CONFIGURATION
CONFIG GSE 1(64) DATA ITEMS
transmitted data
transmitted data
transmitted data
transmitted data

REMOTE
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents