CG.5 DNP Point Lists
CG.5.1 Binary Input / Binary Input Change (Objects 01/02)
60
The point list for Binary Inputs (Object 01) and Binary Input Change (Object 02) is shown
below:
Table CG–5: Binary Inputs (Sheet 1 of 4)
Idx
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
40
Description
Relay In Service
Trip Condition Active
Alarm Condition Active
Simulation Mode Enabled
Breaker Is Open
Breaker Is Closed
Hot Stator Fault Active
Negative Sequence Fault Active
Ground Fault Active
Loss Of Field Fault Active
VT Failure Detected
Breaker Failure Detected
Relay 1 Trip Operated
Relay 2 Auxiliary Operated
Relay 3 Auxiliary Operated
Relay 4 Auxiliary Operated
Relay 5 Alarm Operated
Relay 6 Service Operated
Setpoint Access Input Closed
Breaker Status Input Closed
Assignable Input 1 Closed
Assignable Input 2 Closed
Assignable Input 3 Closed
Assignable Input 4 Closed
Assignable Input 5 Closed
Assignable Input 6 Closed
Assignable Input 7 Closed
Trip Coil Supervision - Coil Detected
Assignable Input 1 Trip Active or Latched
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Class
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1