Neutral Directional Overcurrent (Ansi 67N, Iec Pdef/Ptoc) - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
d) NEUTRAL DIRECTIONAL OVERCURRENT (ANSI 67N, IEC PDEF/PTOC)

PATH: SETTINGS
GROUPED ELEMENTS
 NEUTRAL
 DIRECTIONAL OC1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The neutral directional overcurrent element provides both forward and reverse fault direction indications the
and
OC1 FWD
NEUTRAL DIR OC1 REV
ating current is above a pickup level (overcurrent unit) and the fault direction is seen as forward or reverse, respectively
(directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the either the neutral current calcu-
lated from the phase currents or the ground current. There are separate pickup settings for the forward-looking and
reverse-looking functions. If set to use the calculated 3I_0, the element applies a positive-sequence restraint for better per-
formance: a small user-programmable portion of the positive-sequence current magnitude is subtracted from the zero-
sequence current magnitude when forming the operating quantity.
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
System unbalances under heavy load conditions.
GE Multilin
SETTING GROUP 1(6)
NEUTRAL CURRENT
NEUTRAL DIR OC1
FUNCTION: Disabled
NEUTRAL DIR OC1
SOURCE: SRC 1
NEUTRAL DIR OC1
POLARIZING: Voltage
NEUTRAL DIR OC1 POL
VOLT: Calculated V0
NEUTRAL DIR OC1 OP
CURR: Calculated 3I0
NEUTRAL DIR OC1 POS-
SEQ RESTRAINT: 0.063
NEUTRAL DIR OC1
OFFSET: 0.00 
NEUTRAL DIR OC1 FWD
ECA: 75° Lag
NEUTRAL DIR OC1 FWD
LIMIT ANGLE: 90°
NEUTRAL DIR OC1 FWD
PICKUP: 0.050 pu
NEUTRAL DIR OC1 REV
LIMIT ANGLE: 90°
NEUTRAL DIR OC1 REV
PICKUP: 0.050 pu
NEUTRAL DIR OC1 BLK:
Off
NEUTRAL DIR OC1
TARGET: Self-reset
NEUTRAL DIR OC1
EVENTS: Disabled
operands, respectively. The output operand is asserted if the magnitude of the oper-
I
3
I_0
K
I_1
=
op
T60 Transformer Protection System
5.6 GROUPED ELEMENTS

NEUTRAL DIRECTIONAL OC1
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Voltage, Current, Dual, Dual-V, Dual-I
Range: Calculated V0, Aux. Voltage (VX)
Range: Calculated 3I0, Measured IG
Range: 0.000 to 0.500 in steps of 0.001
Range: 0.00 to 250.00
in steps of 0.01
Range: –90 to 90° in steps of 1
Range: 40 to 90° in steps of 1
Range: 0.006 to 30.000 pu in steps of 0.001
Range: 40 to 90° in steps of 1
Range: 0.006 to 30.000 pu in steps of 0.001
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
NEUTRAL DIR
(EQ 5.38)
5-237