Differential And Restraint Current Calculations; Transformer Windings Between Two Breakers; Setup Method A (Preferred) - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
h) DIFFERENTIAL AND RESTRAINT CURRENT CALCULATIONS
Differential and restraint currents are calculated as follows:
where
Id
,
Id
, and
Id
are the phase differential currents and
A
B
C
i) TRANSFORMER WINDINGS BETWEEN TWO BREAKERS
When the relay is to protect a transformer with windings connected between two breakers, such as in a ring bus or breaker-
and-a-half station configuration, one of the methods for configuring currents into the relay presented below should be used
(see the Breaker-and-a-Half Scheme diagram in the Overview section of this chapter).
For this example it is assumed that winding 1 is connected between two breakers and winding 2 is connected to a single
breaker. The CTs associated with winding 1 are CTX, at 1200/5 A and CTY, at 1000/5 A. CTX is connected to current input
channels 1 through 3 inclusive and CTY is connected to current input channels 5 through 7 inclusive on a type 8H CT/VT
module in relay slot "F." The CT2 on winding 2 is 5000/5 A and is connected to current input channels 1 through 4 inclusive
on a type 8F CT/VT module in relay slot "M".

SETUP METHOD A (PREFERRED)

This approach is preferred because it provides increased sensitivity as the current from each individual set of CTs partici-
pates directly in the calculation of CT ratio mismatch, phase compensation, zero-sequence removal (if required) and the
differential restraint current. The concept used in this approach is to consider that each set of CTs connected to winding 1
represents a connection to an individual winding. For our example we consider the two-winding transformer to be a three-
winding transformer.
1.
Enter the settings for each set of CTs in the
"1200 A"
PHASE CT F1 PRIMARY:
PHASE CT F1 SECONDARY:
"1 A" (default value)
GROUND CT F1 PRIMARY:
GROUND CT F1 SECONDARY:
"1000 A"
PHASE CT F5 PRIMARY:
PHASE CT F5 SECONDARY:
"1 A" (default value)
GROUND CT F5 PRIMARY:
GROUND CT F5 SECONDARY:
"5000 A"
PHASE CT M1 PRIMARY:
PHASE CT M1 SECONDARY:
GROUND CT M5 PRIMARY:
GROUND CT M5 SECONDARY:
2.
Configure source n (source 1 for this example) as the current from CTX in Winding 1 in the

SOURCES
SOURCE 1(4)
"WDG 1X"
SOURCE 1 NAME:
"F1"
SOURCE 1 PHASE CT:
"None"
SOURCE 1 GROUND CT:
"None"
SOURCE 1 PHASE VT:
"None"
SOURCE 1 AUX VT:
GE Multilin
c
c
1  
2  
Id
I
I
=
+
A
A
A
c
c
1  
2  
Id
I
I
=
+
B
B
B
c
c
1  
2  
Id
I
I
=
+
C
C
C
c
c
1   I
2    I
Ir
max I
=
A
A
A
c
c
1   I
2    I
Ir
max I
=
B
B
B
c
c
1   I
Ir
max I
=
C
C
C
SYSTEM SETUP
"5 A"
"1 A" (default value)
"5 A"
"1 A" (default value)
"5 A"
"5000 A"
"5 A"
settings menu.
T60 Transformer Protection System
c
I
w
+
+
A
total
c
I
w
+
+
B
total
c
I
w
+
+
C
total
c
w
A
total
c
w
B
total
c
2    I
w
C
total
Ir
,
Ir
, and
Ir
are the phase restraint currents.
A
B
C
AC INPUTS
CURRENT BANK
5.4 SYSTEM SETUP
(EQ 5.21)
(EQ 5.22)
(EQ 5.23)
(EQ 5.24)
(EQ 5.25)
(EQ 5.26)
settings menu.

SYSTEM SETUP
SIGNAL
5-117
5

Advertisement

Table of Contents
loading

Table of Contents