APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 74)
ADDR
REGISTER NAME
Transformer Thermal Inputs (Read/Write Command)
6180
Transformer Loss of Life Clear Command
Transformer Percent Differential (Read/Write Grouped Setting)
61C0
Percent Differential Function
61C1
Percent Differential Pickup
61C2
Percent Differential Slope 1
61C3
Percent Differential Break 1
61C4
Percent Differential Break 2
61C5
Percent Differential Slope 2
61C6
Inrush Inhibit Function
61C7
Inrush Inhibit Level
61C8
Overexcitation Inhibit Function
61C9
Overexcitation Inhibit Level
61CA
Percent Differential Block
61CC
Percent Differential Target
61CD
Percent Differential Events
61CE
Transformer Inrush Inhibit Mode
Transformer Inst Differential (Read/Write Grouped Setting)
61DA
Inst Differential Function
61DB
Inst Differential Pickup
61DC
Inst Differential Block
61DE
Inst Differential Target
61DF
Inst Differential Events
Overfrequency (Read/Write Setting) (4 Modules)
6470
Overfrequency 1 Function
6471
Overfrequency 1 Block
6473
Overfrequency 1 Source
6474
Overfrequency 1 Pickup
6475
Overfrequency 1 Pickup Delay
6476
Overfrequency 1 Reset Delay
6477
Overfrequency 1 Target
6478
Overfrequency 1 Events
6479
Reserved (4 items)
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
65CD
Power Swing Detect Delay 2 Pickup
65CE
Power Swing Detect Delay 3 Pickup
65CF
Power Swing Detect Delay 4 Pickup
65D0
Power Swing Detect Seal In Delay
GE Multilin
RANGE
0 to 1
0 to 1
0.05 to 1
15 to 100
1 to 2
2 to 3
50 to 100
0 to 2
1 to 40
0 to 1
1 to 40
0 to 4294967295
0 to 2
0 to 1
0 to 2
0 to 1
2 to 30
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 4294967295
0 to 5
20 to 65
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
40 to 140
40 to 140
40 to 140
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
T60 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F126
---
1
F102
pu
0.001
F001
%
1
F001
pu
0.001
F001
pu
0.001
F001
%
1
F001
---
1
F168
%fo
0.1
F001
---
1
F169
%fo
0.1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F189
---
1
F102
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F167
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
DEFAULT
0 (No)
0 (Disabled)
100
B
25
2000
8000
100
1 (Adapt. 2nd)
200
0 (Disabled)
100
0
0 (Self-reset)
0 (Disabled)
0 (Per phase)
0 (Disabled)
8000
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0 (SRC 1)
6050
500
500
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75
120
90
60
30
50
17
9
17
400
B-43