Digital Elements; Digital Element Scheme Logic - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
CONTROL ELEMENTS
 DIGITAL ELEMENT 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name which will be referenced in any target message, a blocking input from any selected FlexLogic oper-
and, and a timer for pickup and reset delays for the output operand.
DIGITAL ELEMENT 1 INPUT: Selects a FlexLogic operand to be monitored by the digital element.
DIGITAL ELEMENT 1 PICKUP DELAY: Sets the required time delay from element pickup to element operation. If a
pickup delay is not required, set to "0". To avoid nuisance alarms, set the delay greater than the operating time of the
breaker.
DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to "0".
DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to
"Disabled", the operation of the pickup LED is blocked.
SETTING
DIGITAL ELEMENT 01
FUNCTION:
Enabled = 1
SETTING
DIGITAL ELEMENT 01
INPUT:
Off = 0
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0
GE Multilin


DIGITAL ELEMENTS

DIGITAL ELEMENT
FUNCTION: Disabled
DIG ELEM
1 NAME:
Dig Element 1
DIG ELEM
1 INPUT:
Off
DIG ELEM
1 PICKUP
DELAY:
0.000 s
DIG ELEM
1 RESET
DELAY:
0.000 s
DIG ELEMENT
1
PICKUP LED: Enabled
DIG ELEM
1 BLOCK:
Off
DIGITAL ELEMENT
TARGET: Self-reset
DIGITAL ELEMENT
EVENTS: Disabled
SETTING
DIGITAL ELEMENT 01
NAME:
AND
RUN
INPUT = 1
Figure 5–145: DIGITAL ELEMENT SCHEME LOGIC
T60 Transformer Protection System
5.7 CONTROL ELEMENTS
DIGITAL ELEMENT 1(48)
Range: Disabled, Enabled
1
Range: 16 alphanumeric characters
Range: FlexLogic operand
Range: 0.000 to 999999.999 s in steps of 0.001
Range: 0.000 to 999999.999 s in steps of 0.001
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
1
Range: Disabled, Enabled
1
SETTINGS
DIGITAL ELEMENT 01
PICKUP DELAY:
DIGITAL ELEMENT 01
RESET DELAY:
t
PKP
t
RST
5.7.9 DIGITAL ELEMENTS
FLEXLOGIC OPERANDS
DIG ELEM 01 DPO
DIG ELEM 01 PKP
DIG ELEM 01 OP
827042A2.VSD
5-287
5