GE
Grid Solutions
750/760 Feeder Management Relay
Chapter 6: DNP Point Lists
Binary Input / Binary Input Change
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DNP Point Lists
The point list for Binary Input (Object 01) and Binary Input Change (Object 02) is shown
below.
Table 1: Binary Inputs DNP Points
Index
Description
0
Relay In Service
1
Trip Condition(s) Active
2
Alarm Condition(s) Active
3
Protection Picked Up
4
Setpoint Group 1 Active
5
Setpoint Group 2 Active
6
Setpoint Group 3 Active
7
Setpoint Group 4 Active
8
Breaker Is Open
9
Breaker Is Closed
1
10
Reclosure Enabled
1
11
Reclosure Disabled
12
Reclosure In Progress
13
Reclosure Locked Out
14
Local Mode Active
Event
Class
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
1
Class 1
1
Class 1
Class 1
6 - 1