5.2 PRODUCT SETUP
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
 GGIO1 STATUS
 CONFIGURATION
5
The
NUMBER OF STATUS POINTS IN GGIO1
instantiated in the GGIO1 logical node. Changes to the
the T60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
GGIO2 CF SPSCO 1(64)
 GGIO2 CF SPCSO 1
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are "0"
(status only), "1" (direct control), and "2" (SBO with normal security). The GGIO2 control points are used to control the T60
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
 GGIO4 ANALOG
 CONFIGURATION
The
NUMBER OF ANALOG POINTS
changed, the T60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
5-52

PRODUCT SETUP
COMMUNICATIONS
NUMBER OF STATUS
POINTS IN GGIO1: 8
GGIO1 INDICATION
MESSAGE
Off
GGIO1 INDICATION
MESSAGE
Off
GGIO1 INDICATION
MESSAGE
Off
GGIO1 INDICATION 128
MESSAGE
Off
setting specifies the number of "Ind" (single point status indications) that are

PRODUCT SETUP
COMMUNICATIONS
GGIO2 CF SPCSO 1
CTLMODEL: 1

PRODUCT SETUP
COMMUNICATIONS
NUMBER OF ANALOG
POINTS IN GGIO4:
 GGIO4 ANALOG
MESSAGE
 MEASURED VALUE
 GGIO4 ANALOG
MESSAGE
 MEASURED VALUE
 GGIO4 ANALOG
MESSAGE
 MEASURED VALUE
 GGIO4 ANALOG 32
MESSAGE
 MEASURED VALUE
setting determines how many analog data points will exist in GGIO4. When this value is
T60 Transformer Protection System


IEC 61850 PROTOCOL
Range: 8 to 128 in steps of 8
Range: FlexLogic operand
1
Range: FlexLogic operand
2
Range: FlexLogic operand
3
Range: FlexLogic operand
NUMBER OF STATUS POINTS IN GGIO1


IEC 61850 PROTOCOL
Range: 0, 1, or 2


IEC 61850 PROTOCOL
Range: 4 to 32 in steps of 4
8
1
2
3
5 SETTINGS
GGIO1 STATUS CONFIGURATION
setting will not take effect until
GGIO2 CONTROL CONFIGURATION
GGIO4 ANALOG CONFIGURATION