Directional Mho Distance Characteristic - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
2.
The
MEMORY DURATION
GROUPED ELEMENTS
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8: Theory of operation.
Although all zones can be used as either instantaneous elements (pickup [
time-delayed elements (operate [
tripping mode.
5
PHS DIST Z1 DIR: All phase distance zones are reversible. The forward direction is defined by the
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the
ance defined by
PHS DIST Z1 SHAPE: This setting selects the shape of the phase distance function between the mho and quadrilat-
eral characteristics. The selection is available on a per-zone basis. The two characteristics and their possible varia-
tions are shown in the following figures.
5-184
setting (common for the distance elements of all zones as entered under

SETTING GROUP 1(6)
] FlexLogic operands), only zone 1 is intended for the instantaneous under-reaching
OP
Ensure that the Phase VT Secondary Voltage setting (see the

menu) is set correctly to prevent improper operation of associated mem-
INPUTS
VOLTAGE BANK
ory action.
PHS DIST Z1 REACH
and
PHS DIST Z1 REV REACH
PHS DIST Z1 REV REACH RCA
DIR COMP LIMIT
Figure 5–71: DIRECTIONAL MHO DISTANCE CHARACTERISTIC
T60 Transformer Protection System
).
DISTANCE
] and dropout [
PKP
and
PHS DIST Z1 RCA
as illustrated below.
X
COMP LIMIT
DIR COMP LIMIT
DIR RCA
RCA
837720A1.CDR
5 SETTINGS
SETTINGS
] FlexLogic operands) or
DPO

SETTINGS
SYSTEM SETUP
PHS DIST Z1 RCA
settings, and the reverse reach imped-
R

AC
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents