B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 56 of 74)
ADDR
REGISTER NAME
B39D
...Repeated for module number 16
B3A0
...Repeated for module number 17
B3A3
...Repeated for module number 18
B3A6
...Repeated for module number 19
B3AC
...Repeated for module number 20
B
B3AF
...Repeated for module number 22
B3B2
...Repeated for module number 23
B3B5
...Repeated for module number 24
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B400
Number of Status Indications in GGIO1
B402
IEC 61850 GGIO1 Indication FlexLogic operands (128
items)
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 Modules)
B5A0
IEC 61850 Configurable GOOSE Function
B5A1
IEC 61850 Configurable GOOSE ID
B5C2
Configurable GOOSE Destination MAC Address
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
B5C6
IEC 61850 Configurable GOOSE VLAN ID
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
B5C8
IEC 61850 Configurable GOOSE ConfRev
B5CA
IEC 61850 Configurable GOOSE Retransmission Curve
B5CB
Configurable GOOSE dataset items for transmission
(64 items)
B60B
...Repeated for Module 2
B676
...Repeated for Module 3
B6E1
...Repeated for Module 4
B74C
...Repeated for Module 5
B7B7
...Repeated for Module 6
B822
...Repeated for Module 7
B88D
...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (16 Modules)
B900
Configurable GOOSE dataset items for reception
(32 items)
B920
...Repeated for Module 2
B940
...Repeated for Module 3
B960
...Repeated for Module 4
B980
...Repeated for Module 5
B9A0
...Repeated for Module 6
B9C0
...Repeated for Module 7
B9E0
...Repeated for Module 8
BA00
...Repeated for Module 9
BA20
...Repeated for Module 10
BA40
...Repeated for Module 11
BA60
...Repeated for Module 12
BA80
...Repeated for Module 13
BAA0
...Repeated for Module 14
BAC0
...Repeated for Module 15
BAE0
...Repeated for Module 16
Contact Inputs (Read/Write Setting) (96 Modules)
BB00
Contact Input 1 Name
BB06
Contact Input 1 Events
BB07
Contact Input 1 Debounce Time
BB08
...Repeated for Contact Input 2
BB10
...Repeated for Contact Input 3
BB18
...Repeated for Contact Input 4
B-64
RANGE
8 to 128
0 to 4294967295
0 to 1
---
---
0 to 7
0 to 4095
0 to 16383
1 to 4294967295
0 to 3
0 to 1008
0 to 197
---
0 to 1
0 to 16
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
8
F001
---
1
F300
---
1
F102
---
---
F209
"GOOSEOut_x_"
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F611
---
1
F616
---
1
F233
---
---
F205
---
1
F102
ms
0.5
F001
DEFAULT
8
0
0 (None)
0
4
0
0
1
3 (Relaxed)
0 (None)
0 (None)
"Cont Ip 1"
0 (Disabled)
20