Dnp Point Lists; Binary Input / Binary Input Change (Objects 01/02) - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

6 COMMUNICATIONS

6.5 DNP POINT LISTS

POINT LIST FOR: BINARY INPUT (OBJECT 01)
BINARY INPUT CHANGE (OBJECT 02)
(SHEET 1 OF 4)
INDEX
DESCRIPTION
0
Relay In Service
1
Trip Condition Active
2
Alarm Condition Active
3
Simulation Mode Enabled
4
Breaker Is Open
5
Breaker Is Closed
6
Hot Stator Fault Active
7
Negative Sequence Fault Active
8
Ground Fault Active
9
Loss Of Field Fault Active
10
VT Failure Detected
11
Breaker Failure Detected
12
Relay 1 Trip Operated
13
Relay 2 Auxiliary Operated
14
Relay 3 Auxiliary Operated
15
Relay 4 Auxiliary Operated
16
Relay 5 Alarm Operated
17
Relay 6 Service Operated
18
Setpoint Access Input Closed
19
Breaker Status Input Closed
20
Assignable Input 1 Closed
21
Assignable Input 2 Closed
22
Assignable Input 3 Closed
23
Assignable Input 4 Closed
24
Assignable Input 5 Closed
25
Assignable Input 6 Closed
26
Assignable Input 7 Closed
27
Trip Coil Supervision - Coil Detected
28
... Reserved ...
39
... Reserved ...
40
Assignable Input 1 Trip Active /
Latched
41
Assignable Input 2 Trip Active /
Latched
42
Assignable Input 3 Trip Active /
Latched
43
Assignable Input 4 Trip Active /
Latched
44
Assignable Input 5 Trip Active /
Latched
45
Assignable Input 6 Trip Active /
Latched
46
Assignable Input 7 Trip Active /
Latched
47
Sequential Trip Active or Latched
GE Power Management

6.5.1 BINARY INPUT / BINARY INPUT CHANGE (OBJECTS 01/02)

POINT LIST FOR: BINARY INPUT (OBJECT 01)
EVENT
INDEX
CLASS
ASSIGNED
Class 1
48
Class 1
49
Class 1
50
Class 1
51
Class 1
Class 1
52
Class 1
53
Class 1
54
Class 1
55
Class 1
56
Class 1
57
Class 1
58
Class 1
59
Class 1
60
Class 1
61
Class 1
62
Class 1
Class 1
63
Class 1
Class 1
64
Class 1
65
Class 1
66
Class 1
67
Class 1
68
Class 1
69
Class 1
70
Class 1
71
Class 1
72
73
74
75
Class 1
76
77
Class 1
78
79
Class 1
80
Class 1
81
82
Class 1
83
Class 1
84
Class 1
85
Class 1
489 Generator Management Relay
6.5 DNP POINT LISTS
BINARY INPUT CHANGE (OBJECT 02)
(SHEET 2 OF 4)
DESCRIPTION
Field-Breaker Discrepancy Trip Active
or Latched
Tachometer Trip Active or Latched
Offline O/C Trip Active or Latched
Inadvertent Energization Trip Active or
Latched
Phase O/C Trip Active or Latched
Neg. Seq. O/C Trip Active or Latched
Ground O/C Trip Active or Latched
Phase Differential Trip Active or
Latched
Undervoltage Trip Active or Latched
Overvoltage Trip Active or Latched
Volts/Hertz Trip Active or Latched
Phase Reversal Trip Active or Latched
Underfrequency Trip Active or Latched
Overfrequency Trip Active or Latched
Neutral O/V (Fund) Trip Active /
Latched
rd
Neutral U/V (3
Harmonic) Trip Active
or Latched
Reactive Power Trip Active or Latched
Reverse Power Trip Active or Latched
Low Fwd Power Trip Active or Latched
Thermal Model Trip Active or Latched
RTD #1 Trip Active or Latched
RTD #2 Trip Active or Latched
RTD #3 Trip Active or Latched
RTD #4 Trip Active or Latched
RTD #5 Trip Active or Latched
RTD #6 Trip Active or Latched
RTD #7 Trip Active or Latched
RTD #8 Trip Active or Latched
RTD #9 Trip Active or Latched
RTD #10 Trip Active or Latched
RTD #11 Trip Active or Latched
RTD #12 Trip Active or Latched
Analog Input 1 Trip Active or Latched
Analog Input 2 Trip Active or Latched
Analog Input 3 Trip Active or Latched
Analog Input 4 Trip Active or Latched
Loss of Excitation Circle 1 Trip Active
or Latched
Loss of Excitation Circle 2 Trip Active
or Latched
EVENT
CLASS
ASSIGNED
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
6
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
6-49