Ieee C37.94 Interface; G.703 And Fiber Interface Connection - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
3
The UR-series IEEE C37.94 communication modules (modules types 2G, 2H, 2I, 2J, 76, and 77) are designed to interface
with IEEE C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input
and output applications. The IEEE C37.94 standard defines a point-to-point optical link for synchronous data between a
multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard provides for speeds up to 64n kbps,
where n = 1, 2,..., 12. The UR-series C37.94 communication modules are either 64 kbps (with n fixed at 1) for 128 kbps
(with n fixed at 2). The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:.
IEEE standard: C37.94 for 1  128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2  64 kbps opti-
cal fiber interface (for 76 and 77 modules)
Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber
Fiber optic mode: multimode
Fiber optic cable length: up to 2 km
Fiber optic connector: type ST
Wavelength: 830 ±40 nm
Connection: as per all fiber optic connections, a Tx to Rx connection is required
The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports
the IEEE C37.94 standard shown as follows.
3-34
Figure 3–42: G.703 AND FIBER INTERFACE CONNECTION
T60 Transformer Protection System
3 HARDWARE

3.3.8 IEEE C37.94 INTERFACE

GE Multilin

Advertisement

Table of Contents
loading

Table of Contents