B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 74)
ADDR
REGISTER NAME
Breaker Control (Read/Write Settings) (4 Modules)
47D0
Breaker 1 Function
47D1
Breaker 1 Name
47D4
Breaker 1 Mode
47D5
Breaker 1 Open
B
47D7
Breaker 1 Close
47D9
Breaker 1 Phase A / Three-pole Closed
47DB
Breaker 1 Phase B Closed
47DD
Breaker 1 Phase C Closed
47DF
Breaker 1 External Alarm
47E1
Breaker 1 Alarm Delay
47E3
Breaker 1 Pushbutton Control
47E4
Breaker 1 Manual Close Recall Time
47E6
Breaker 1 Out of Service
47E8
Breaker 1 Block Open
47EA
Breaker 1 Block Close
47EC
Breaker 1 Phase A / Three-pole Opened
47EE
Breaker 1 Phase B Opened
47F0
Breaker 1 Phase C Opened
47F2
Breaker 1 Operate Time
47F3
Breaker 1 Events
47F4
Reserved
47F5
...Repeated for breaker 2
481A
...Repeated for breaker 3
483F
...Repeated for breaker 4
Demand (Read/Write Setting)
490A
Demand Current Method
490B
Demand Power Method
490C
Demand Interval
490D
Demand Input
Demand (Read/Write Command)
490F
Demand Clear Record
FlexCurve A (Read/Write Setting)
4910
FlexCurve A (120 items)
FlexCurve B (Read/Write Setting)
4988
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 Modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
B-36
RANGE
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 1
0 to 65535
0 to 2
0 to 2
0 to 5
0 to 4294967295
0 to 1
0 to 655535
0 to 655535
0 to 65535
---
---
0 to 65535
---
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
---
1
F102
s
1
F001
---
1
F139
---
1
F139
---
1
F132
---
1
F300
---
1
F126
ms
1
F011
ms
1
F011
---
1
F001
---
---
F202
---
---
F202
---
1
F001
---
---
F001
DEFAULT
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
0
0
70
0 (Disabled)
0
0 (Thermal
Exponential)
0 (Thermal
Exponential)
2 (15 MIN)
0
0 (No)
0
0
0
" "
""
0
0
GE Multilin