Phase Instantaneous Overcurrent (Ansi 50P, Iec Pioc); Phase Instantaneous Overcurrent 1 Scheme Logic - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
d) PHASE INSTANTANEOUS OVERCURRENT (ANSI 50P, IEC PIOC)

PATH: SETTINGS
 PHASE IOC1
5
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan-
taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A).
5-230
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE IOC1
FUNCTION: Disabled
PHASE IOC1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE IOC1
MESSAGE
PICKUP:
PHASE IOC1 PICKUP
MESSAGE
DELAY:
PHASE IOC1 RESET
MESSAGE
DELAY:
PHASE IOC1 BLOCK A:
MESSAGE
Off
PHASE IOC1 BLOCK B:
MESSAGE
Off
PHASE IOC1 BLOCK C:
MESSAGE
Off
PHASE IOC1
MESSAGE
TARGET: Self-reset
PHASE IOC1
MESSAGE
EVENTS: Disabled
Figure 5–108: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC
T60 Transformer Protection System
PHASE CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 30.000 pu in steps of 0.001
1.000 pu
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
PHASE IOC 1(6)