Iec 61850 Implementation Via Enervista Ur Setup; Overview; C.5.1 Overview - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

APPENDIX C
C.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
The T60 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1.
An ICD file is generated for the T60 by the EnerVista UR Setup software that describe the capabilities of the IED.
2.
The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3.
The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
The following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC
61850:
BDA: Basic Data Attribute, that is not structured
DAI: Instantiated Data Attribute
DO: Data Object type or instance, depending on the context
GE Multilin
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
Figure C–1: IED CONFIGURATION PROCESS
T60 Transformer Protection System