Alarm Status - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

5 ACTUAL VALUES
Õ
PATH: ACTUAL VALUES
n ALARM STATUS
n [ENTER] for more
GE Multilin
Courtesy of NationalSwitchgear.com
Õ×
A1 STATUS

ALARM STATUS

ð
NO ALARMS
ENTER
ESCAPE
REMOTE ALARM
ESCAPE
STATUS: Active
MESSAGE
PRESSURE SWITCH
ESCAPE
ALARM STATUS: Active
MESSAGE
VIBRATION SWITCH
ESCAPE
ALARM STATUS: Active
MESSAGE
DIG. COUNTER ALARM:
ESCAPE
1 000 000 000 Units
MESSAGE
TACHOMETER
ESCAPE
ALARM: 3000 RPM
MESSAGE
GENERAL SW. A
ESCAPE
ALARM STATUS: Active
MESSAGE
THERMAL CAPACITY
ESCAPE
ALARM: 100% USED
MESSAGE
XX.XX x FLA OVERLOAD
ESCAPE
TIME TO TRIP: XXXXX s
MESSAGE
UNDERCURRENT ALARM
ESCAPE
Ia = 85 A
MESSAGE
CURRENT UNBALANCE
ESCAPE
ALARM: 15%
MESSAGE
GROUND FAULT
ESCAPE
ALARM: 25.3 A
MESSAGE
STATOR RTD #1
ESCAPE
MESSAGE
ALARM: 135°C
OPEN SENSOR ALARM:
ESCAPE
RTD # 1 2 3 4 5 6...
MESSAGE
SHORT/LOW TEMP ALARM
ESCAPE
RTD # 7 8 9 10 11...
MESSAGE
UNDERVOLTAGE ALARM
ESCAPE
Vab= 3245 V
MESSAGE
OVERVOLTAGE ALARM
ESCAPE
Vab= 4992 V
MESSAGE
SYSTEM FREQUENCY
ESCAPE
ALARM: 59.4 Hz
MESSAGE
POWER FACTOR
ESCAPE
ALARM
PF: 0.00
MESSAGE
469 Motor Management Relay
Range: N/A
Message seen when no alarms are active
Range: Active, Latched. The first line of this message
reflects the Switch Name as programmed. The
status is Active if the condition that caused the
alarm is still present
Range: Active, Latched. Status is Active if condition
causing the Alarm still present
Range: Active, Latched. Status is Active if condition
causing the Alarm still present
Range: 1 to 9999999999
Displays current value of digital counter
Range: 0 to 3600 RPM
Displays current Tachometer Digital Input value
Range: Active, Latched. The first line of this message
reflects the Switch Name as programmed. The
status is Active if the condition that caused the
alarm is still present
Range: 1 to 100
Thermal Capacity Used value is shown here
Range: 0 to 99999 sec.
Displays overload level and estimated time to trip
Range: 1 to 5000 A; 5 to 99% FLA
Value of lowest phase current is shown here
85% FLA
Range: 0 to 100%
Reflects the present unbalance level
Range: 0.1 to 5000 A
Reflects the present ground current level
Range: –50 to 250°C. The first line of this alarm message
reflects the RTD Name as programmed. Reflects
present RTD temperature
Range: the RTD number with the open sensor as
programmed for RTDs 1 to 12
Range: 1 to 12
Shows RTD with the short/low temperature alarm
Range: 0 to 20000 V; 50 to 99% of Rated
Value of lowest line-to-line voltage is shown here
78% Rated
Range: 0 to 20000 V; 101 to 150% of Rated
Value of lowest line-to-line voltage is shown here
120%
Range: 0.00, 20.00 to 120.00 Hz
System voltage frequency value is shown here
Range: 0.00 to 0.99 Lead or Lag, 0.00, 1.00
Current Power Factor is shown here
5.2 A1 STATUS
5.2.3 ALARM STATUS
5
5-5