GE 469 Instruction Manual page 71

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

4 SETPOINTS
h) VIBRATION SWITCH ALARM
Õ×
PATH: SETPOINTS
S3 DIGITAL INPUTS
n ASSIGNABLE INPUT 1
n [ENTER] for more
Once the Vibration Switch Alarm function is chosen for one of the assignable digital inputs, the setpoint messages shown
here will follow the assignment message. When the motor is stopped or running, the digital input will be monitored. If a clo-
sure occurs, after the specified delay, an alarm will occur.
i) VIBRATION SWITCH TRIP
Õ×
PATH: SETPOINTS
S3 DIGITAL INPUTS
n ASSIGNABLE INPUT 1
n [ENTER] for more
Once the Vibration Switch Trip function is chosen for one of the assignable digital inputs, the setpoint messages shown
here will follow the assignment message. When the motor is stopped or running, the digital input will be monitored. If a clo-
sure occurs, after the specified delay, a trip will occur.
GE Multilin
Courtesy of NationalSwitchgear.com
Õ×
ASSIGNABLE INPUT 1(4)
ð
INPUT 1 FUNCTION:
ENTER
ESCAPE
Vibration Sw Alarm
VIBRATION SWITCH
ESCAPE
ALARM: Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
VIBRATION SW. ALARM
ESCAPE
DELAY: 5.0 s
MESSAGE
VIBRATION SW. ALARM
ESCAPE
EVENTS: Off
MESSAGE
Õ×
ASSIGNABLE INPUT 1(4)
ð
INPUT 1 FUNCTION:
ENTER
Vibration Sw Trip
ESCAPE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
VIBRATION SW. TRIP
ESCAPE
DELAY: 5.0 s
MESSAGE
469 Motor Management Relay
4.4 S3 DIGITAL INPUTS
Range: See above. The following setpoints apply only if
INPUT 1(4) FUNCTION
is "Vibration Sw Alarm".
Range: Latched, Unlatched. Only seen if
is "Vibration Sw Alarm"
FUNCTION
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3,
Auxiliary3. Only seen if
INPUT 1(4) FUNCTION
is "Vibration Sw Alarm"
Range: 0.1 to 100.0 s in steps of 0.1. Only seen if
1(4) FUNCTION
is "Vibration Sw Alarm"
Range: On, Off. Only seen if
INPUT 1(4) FUNCTION
"Vibration Sw Alarm"
Range: See above. The following setpoints apply only if
INPUT 1(4) FUNCTION
is "Vibration Sw Trip".
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3. Only seen if
FUNCTION
is "Vibration Sw Trip"
Range: 0.1 to 100.0 s in steps of 0.1. Only seen if
1(4) FUNCTION
is "Vibration Sw Trip"
INPUT 1(4)
INPUT
is
4
INPUT 1(4)
INPUT
4-21

Hide quick links:

Advertisement

Table of Contents
loading