4 SETPOINTS
Õ×
PATH: SETPOINTS
S13 469 TESTING
n FAULT SETUP
n [ENTER] for more
The values entered under Fault Values will be substituted for the measured values in the 469 when the simulation mode is
"Simulate Fault".
GE Multilin
Courtesy of NationalSwitchgear.com
Õ×

FAULT SETUP

ð
FAULT CURRENT
ENTER
ESCAPE
PHASE A: 0.00 x CT
FAULT CURRENT
ESCAPE
PHASE B: 0.00 x CT
MESSAGE
FAULT CURRENT
ESCAPE
PHASE C: 0.00 x CT
MESSAGE
FAULT GROUND
ESCAPE
CURRENT: 0.0 A
MESSAGE
FAULT VOLTAGES
ESCAPE
VLINE: 1.00 x RATED
MESSAGE
FAULT CURRENT
ESCAPE
MESSAGE
LAGS VOLTAGE: 0°
FAULT DIFF AMPS
ESCAPE
IDIFF: 0.00 x CT
MESSAGE
FAULT STATOR
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT BEARING
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT OTHER
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT AMBIENT
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT SYSTEM
ESCAPE
FREQUENCY: 60.0 Hz
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 1: 0%
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 2: 0%
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 3: 0%
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 4: 0%
MESSAGE
469 Motor Management Relay
4.14 S13 469 TESTING
4.14.3 FAULT SETUP
Range: 0.00 to 20.00 x CT in steps of 0.01
Range: 0.00 to 20.00 x CT in steps of 0.01
Range: 0.00 to 20.00 x CT in steps of 0.01
Range: 0.0 to 5000.0 A in steps of 0.1
Range: 0.00 to 1.10 x RATED in steps of 0.01
Range: 0 to 359° in steps of 1
Range: 0.00 to 1.10 x RATED in steps of 0.01
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 45.0 to 70.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1