4 SETPOINTS
Õ×
PATH: SETPOINTS
S12 ANALOG I/O
n ANALOG INPUT 1
n [ENTER] for more
There are 4 analog inputs, 4 to 20 mA, 0 to 20 mA, or 0 to 1 mA as selected. These inputs may be used to monitor trans-
ducers such as vibration monitors, tachometers, pressure transducers, etc. These inputs may be used for alarm and trip-
ping purposes. The inputs are sampled every 50 ms. The level of the analog input is also available over the
communications port.
Before the input may be used, it must be configured. A name may be assigned for the input, units may be assigned, and a
minimum and maximum value may be assigned. Also, the trip and alarm features may be blocked from start for a specified
time delay. If the block time is 0, there is no block and the trip and alarm features will be active when the motor is stopped
GE Multilin
Courtesy of NationalSwitchgear.com
Õ×
ANALOG INPUT 1(4)
ð
ANALOG INPUT 1:
ENTER
ESCAPE
Disabled
ANALOG INPUT 1 NAME:
ESCAPE
Analog I/P 1
MESSAGE
ANALOG INPUT 1 UNITS:
ESCAPE
Units
MESSAGE
ANALOG INPUT 1
ESCAPE
MINIMUM: 0
MESSAGE
ANALOG INPUT 1
ESCAPE
MAXIMUM: 100
MESSAGE
ANALOG INPUT 1 BLOCK
ESCAPE
MESSAGE
FROM START: 0 s
ANALOG INPUT 1
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
LEVEL: 10 Units
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
MESSAGE
PICKUP: Over
ANALOG INPUT 1 ALARM
ESCAPE
DELAY: 0.1 s
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
EVENTS: Off
MESSAGE
ANALOG INPUT 1
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
ANALOG INPUT 1 TRIP
ESCAPE
LEVEL: 20 Units
MESSAGE
ANALOG INPUT 1 TRIP
ESCAPE
PICKUP: Over
MESSAGE
ANALOG INPUT 1 TRIP
ESCAPE
MESSAGE
DELAY: 0.1 s
469 Motor Management Relay
4.13 S12 ANALOG I/O

4.13.2 ANALOG INPUTS 1 TO 4

Range: Disabled, 4-20 mA, 0-20 mA, 0-1 mA
Range: 12 alphanumeric characters
Range: 6 alphanumeric characters
Range: –50000 to 50000 in steps of 1
Range: –50000 to 50000 in steps of 1
Range: 0 to 5000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3,
Auxiliary3
Range: –50000 to 50000 in steps of 1
Units reflect
ANALOG INPUT 1 UNITS
Range: Over, Under
Range: 0.1 to 300.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3
Trip & Auxiliary3
Range: –50000 to 50000 in steps of 1
Units reflect
ANALOG INPUT 1 UNITS
Range: Over, Under
Range: 0.1 to 300.0 s in steps of 0.1
4
above
above
4-73