1.2 SPECIFICATIONS
TYPE TESTS
Dielectric Strength:
1
Insulation Resistance: IEC255-5 500 V DC, from relays, CTs, VTs,
DO NOT CONNECT FILTER GROUND TO SAFETY
GROUND DURING DIELECTRIC STRENGTH OR INSU-
LATION RESISTANCE TESTS!
WARNING
Transients:
Impulse Test:
RFI:
EMI:
Static:
Humidity:
Temperature:
Environment:
Vibration:
1-8
Courtesy of NationalSwitchgear.com
Per IEC 255-5 and ANSI/IEEE C37.90
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
power supply to Safety Ground
ANSI C37.90.1 Oscillatory (2.5kV/
1MHz);
ANSI C37.90.1 Fast Rise (5kV/10ns);
Ontario Hydro A-28M-82; IEC255-4
Impulse/High Frequency Disturbance,
Class III Level
IEC 255-5 0.5 Joule 5 kV
50 MHz/15 W Transmitter
C37.90.2 Electromagnetic Interference
at 150 MHz and 450 MHz, 10 V/m
IEC 801-2 Static Discharge
95% non-condensing
–40°C to +60°C ambient
IEC 68-2-38 Temperature/Humidity
Cycle
Sinusoidal Vibration 8.0 g for 72 hrs.
Specifications are subject to change without notice!
469 Motor Management Relay
PACKAGING
12" × 11" × 10" (W × H × D)
Shipping Box:
30.5cm × 27.9cm × 25.4cm
Shipping Weight:
17 lbs Max / 7.7 kg
CERTIFICATION
ISO:
Manufactured under an ISO9001 regis-
tered system.
UL:
UL approved
CSA:
CSA approved
CE:
conforms to EN 55011/CISPR 11, EN
50082-2
IEC:
conforms to IEC 947-1,1010-1