GE 469 Instruction Manual page 45

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

3 USER INTERFACES
e) UPGRADING SETPOINT FILES TO A NEW REVISION
It may be necessary to upgrade the revision code for a previously saved setpoint file after the 469 firmware has been
upgraded.
1.
Establish communications with the relay.
2.
Select the Actual > Product Information menu item and record the Main Revision identifier of the relay firmware; for
example, 30D270A8.000, where 270 is the Main Revision identifier and refers to firmware version 2.70.
3.
Select the File > Open menu item and enter the location and file name of the saved setpoint file to be downloaded to
the connected relay. When the file is open, the 469PC software will be in "File Editing" mode and "Not Communicat-
ing".
4.
Select the File > Properties menu item and note the version code of the setpoint file. If the version code of the set-
point file (e.g. 2.6X) is different than the Main Revision code of the firmware (as noted in Step 1, as 270), use the pull-
down tab to expose the available revision codes and select the one which matches the firmware.
For example:
Firmware revision: 30D270A8.000
current setpoint file version: 2.6X
change setpoint file version to: 2.7X
5.
Select the File > Save menu item to save the setpoint file in the new format.
6.
See Section c): Loading Setpoints from a File for instructions on downloading this setpoint file to the 469.
f) PRINTING SETPOINTS AND ACTUAL VALUES
Use the following procedure to print a list of setpoints:
1.
Select the File > Open menu item and open a previously saved setpoint file,
OR establish communications with the 469.
2.
Select the File > Print Setup menu item, select either Setpoints (All) or Setpoints (Enabled Features) and click OK.
3.
Select the File > Print menu item to send the setpoint file to a printer.
Use the following procedure to print a list of actual values:
1.
Establish communications with the 469.
2.
Select the File > Print Setup menu item, select Actual Values and click OK.
3.
Select the File > Print menu item to send the actual values file to a printer.
GE Multilin
Courtesy of NationalSwitchgear.com
Figure 3–6: SETPOINT FILE VERSION
469 Motor Management Relay